stainless steel tunnel ointment rapid freezer
(2022年07月29日)Main functional parameters of the refrigerator
★ Reliable password protection ★ Over temperature, overload, phase sequence, high and low voltage protection
★ Manual/automatic frost, quick start ★ Temperature control range: ±50°C (resolution 0.1°C
★ Defrost cycle: 0-50 hours (adjustable) ★ Defrost time: 0-100 minutes (adjustable)
★ Defrost end temperature: 0-30℃ (adjustable) ★ High and low temperature protection: ±50℃ (adjustable)
★ Load current: 5A (AC220V/380V) ★ Delayed startup after defrosting: 0-10 minutes
★ Boot delay: 1. Fan 0-90 minutes 2. Compressor 0-30 minutes 3. Condenser 0-30 minutes
★ Shutdown delay: 1. Fan 0-90 minutes 2. Compressor 0-30 minutes 3. Condenser 0-30 minutes 4. Solenoid valve 0-10 minutes
Parameter item and parameter value description:
code
Function
Predetermined area
Factory setting
unit
illustrate
1
U
upper temperature limit
-49~﹢50
5
℃
Cooling start temperature
D
Lower temperature limit
-50~+49
0
℃
Cooling stop temperature
H
Defrost time
0~100
10
minute
The length of each defrosting time
L
defrost cycle
0~50
0.5
Hour
The time between two defrosts
C
High temperature alarm temperature
-20℃~50
10
℃
Alarm when the room temperature exceeds the set value
F
Low temperature alarm temperature
-50~20
-10
℃
Alarm when the room temperature is lower than the set value
b
Defrost end temperature
0~30
20
℃
The wing temperature is equal to the set value and the defrost is over
2
A
Compressor delayed start
0~30
1
minute
Compressor delay start time
b
Delay start of cooling fan
0~30
2
minute
Condenser delay start time
c
Delay start of cooling fan
0~90
3
minute
Delay start time of cooling fan
3
A
Compressor delay stop
0~30
1
minute
Compressor delay stop time
b
Condenser delay stop
0~30
2
minute
Condenser delay stop time
c
Delay stop of cooling fan
0~90
3
minute
Delay time for cooling fan to stop
d
Solenoid valve delay stop
0~10
4
minute
Solenoid valve delay stop time
E
Defrost stop delay
0~10
5
minute
Defrosting stop delay time
Refrigeration, defrost, delay
When the measured value of the room temperature probe is greater than or equal to the upper limit of the temperature, the refrigeration relay is closed and the compressor starts to work. When the measured value of the room temperature probe is less than or equal to the lower temperature limit, the refrigeration relay is disconnected and the compressor stops working. When the defrosting cycle time is up, the refrigeration relay is disconnected, the defrosting relay is pulled in, and defrosting is performed; when the defrosting time is up, the defrosting relay is disconnected and the defrosting is over.
● Quick start: Press the ← key for 3 seconds to start the work quickly after power on.
● Manual defrosting: press the ▲ key for 3 seconds during work to enter the defrosting work.
● Cancel the defrosting function: when the defrosting cycle or defrosting time setting parameter is "0", the defrosting function is canceled.
● Delay: when the compressor, fan, condenser, solenoid valve and defrost relay are on and off, it will lead, lag off and close according to its set parameters. If the set parameter is "0", the delay function will be canceled.