LBS 24KV 630a SF6 Gas Load Break Switch
(2024年06月06日)https://www.zhgopower.com/products/24kv-sf6-gas-load-break-switch.html
LBS 24KV 630a SF6 Gas Load Break Switch
24kV SF6 load break switch is a sf6 load break switch for medium voltage switchgear, using SF6 gas as arc extinguishing and insulating medium. Rate voltage was 24kV, rate current was630A
LBS 24KV 630a SF6 Gas Load Break Switch Application
The SF6 LBS 24kv 630A gas-insulated switch is a three-phase interoperable switching device designed for use in electrical distribution cabinet cabling and overhead power line segment applications.
The 24KV pole mounted disconnect switch can be operated manually in the field or remotely from the control center.
LBS 24KV 630a SF6 Gas Load Break Switch Technical Parameters
Products Type
FWX-24
Basic Ratings
Maximum System Voltage
24kV
Rated Continuous Current
630A
Rated Frequency
50/60Hz
Short Time Withstand Current
16kA/1sec
Making and Breaking Capacity
Mainly Active Load Current
630A
Number of Load-break Operations
400times
Short-circuit Making Current (peak)
40kA
Number of Making Operations
5 times
Cable Charging Current
25A
Line Charging Current
1.5A
Closed Loop Circuit Current
630A
Transformer Magnetizing Current
22A
Power Frequency Withstand Current Test
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters
50kV
DryCondition-1min,Ph- Ph, Phase to Earth
64kV
Dry Condition - 1 min Across Interrupter
79kV
Impulse Withstand Current Test( 1.2 x 50 µs )
Phase to Phase, Phase to Earth
125kV
Across Interrupter
145kV
Other Ratings & Specifications
Internal Arc Test
20kA /0.1 sec
Arc Extinction Medium
SF6 Gas
Insulation Medium
SF6 Gas
Creepage Distance (Porcelain)
700mm
Creepage Distance (Silicon)
1200mm
Dry arcing distance
≥
IP Level
65
Operation Performance
Closing/Opening Time
<1sec
Mechanical Operations (Guaranteed)
10000times
Operating Temperature (*Manual Type)
-25~+70℃
Gas Pressure
Nominal Pressure (MPa, at 20°C)
0.07
Bursting Pressure (MPa)
0.4~0.6
Minimum Gas Pressure (MPa)
0.05
Leakage Rate (cc/ sec)
≤0.5%
Voltage sensors
CT ABC 10P10 5VA
400:05:00
Incoming side and outgoing side of the voltage sensor
6 Voltage sensor(built-in)
Phase voltage:(24(36)kV/√3)/(3.25V/√3)
Special attention should be paid to the voltage sensor, which must be directly fed by the LBS load break switch.
No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately.
If you are looking for a reliable electric power equipment company, please choose us, and we will be your best partner.