SPD for Network / Data Line Surge Protector
(2023年04月04日)https://www.techwinspd.com/products/spd-for-network-data-line-surge-protector.html
Data line surge protector series are mainly used in TCP/IP communication networks to protect electrical and electronic equipment's signal line from the impact of lightning electromagnetic pulse, induced over-voltage, transient operation, and resonance overvoltage.
Features Of SPD For Network / Data Line Surge Protection
Multi. Protection circuits, Gas-Tube+ TVS technology
Dual protection in Common mode and differential mode
TVS array technology, low capacitance
Multi-Strike Capability
RJ45 connector
Application Of SPD For Network / Data Line Surge Protector
CAT5e and CAT5 compatible
10/100 Base-T Ethernet protection
LAN, FDDI, CDDI, ATM
PDH, SDH, SPDH
Industrial control
Loss prevention system device; Security system; Security integration.
IASP; VSCS; ESA; ACS; exit-inlet control system; exit-inlet control system
Installation And Wiring Diagram Of SPD For Network / Data Line Surge Protector
Specification Of SPD For Network / Data Line Surge Protector
ModelD05J4D05J4-8D05J4-16D05J4-24D05J8H
Lightning projection zone(LPZ)2
Standards ComplianceIEC61000, EN60950,GB/T18802.21-2002,TB/T2311-2002
According to IEC61643III
According to DIN VDE6075 Part6(Draft 11.89) A1,A2D
Max continuous operating voltage Uc5V
Nominal discharge current (8/20µs) In3KA
Max discharge current Imax (8/21µs) Imax5KA
Voltage protection Level≤55V
@C2(8/20µs) Up
Voltage protection Level≤25V
@C3(1kV/µs) Up
Rated load current IL200mA
Limiting Voltage(10/700µs)≤20V
Cut-off Frequency fG250MHz
Response time tA (L-N/N-PE)1ns
Protection line1/2,3/61/2,3/6,4/5,7/8
Protection port1816241
MountingBe Installed between protected equipment and signal line
Adapt Transmission rate 100Mbps 1000Mbps
Transmission standards100BaseT/ 1000BaseT/1000Base TX,CAT5/CAT6
Dimension190 (H)×85(W)×48(L)mm482 (H)×86(W)×44(L)mm83 (H)×25(W)×25(L)mm
85(H)×25(W)×25(L)mm
Interface formRJ45
IP code(IEC EN 60529)IP20
Error rate≤10-12
Material/colorAluminum/Blue
Insertion loss≤.3.0dB
Working conditionsTemperature: -40 to 85℃, Relative humidity: ≤95%
As one of lightning protection companies, we can offer sorts of related products for sale, anything you need, please contact us.